Operational Conditions of Plate Heat Exchangers

Consider these aspects when operating plate heat exchangers:

  • Avoid liquid hammers.
  • Ensure the device operates within permitted flow media, pressure, and temperature conditions.
  • Ensure proper venting of the exchanger.

Standard Operating Procedure for Plate Heat Exchangers

Employ the following essential procedure

  • Begin with the cold circuit.
  • Completely vent the system.
  • Shut the cock located between the pump and exchanger.
  • Open the return line cock from the exchanger fully.
  • Start the pump circulation as usual.
  • Smoothly open the shut-off cock between the pump and exchanger.
  • Re-vent the system if required.

Precautions for Temporary Shutdown

Follow these precautions:

  • Close the control cock on the hot circuit while maintaining complete flow in the cold circuit.
  • Deactivate the hot circuit pump.
  • Allow the exchanger to cool down.
  • Shut the cold circuit control cock.
  • Turn off the cold circuit pump.
  • Close all remaining shut-off valves.

Long-term Shutdown Precautions

Steps for disconnecting the unit include:

  • Never open a heat exchanger when hot; allow cooling first.
  • Reduce both fluid pressures.
  • Fully drain all fluids from the unit.
  • Lubricate all bolts.
  • Loosen the setting bolts until the plate pack is relaxed.
  • Refrain from removing tie bolts.
  • Cover the plate pack to shield it from sunlight.